Advanced Search
    YANG Guangyu, HUANG Hao, PAN Hongliang, WAN Jing, SHI Peng, SHI Fangjie. Low-Frequency Electromagnetic Detection and Evaluation of Seawater Pipeline Corrosion in Nuclear Power Plants[J]. Corrosion & Protection, 2025, 46(10): 73-78. DOI: 10.11973/fsyfh230359
    Citation: YANG Guangyu, HUANG Hao, PAN Hongliang, WAN Jing, SHI Peng, SHI Fangjie. Low-Frequency Electromagnetic Detection and Evaluation of Seawater Pipeline Corrosion in Nuclear Power Plants[J]. Corrosion & Protection, 2025, 46(10): 73-78. DOI: 10.11973/fsyfh230359

    Low-Frequency Electromagnetic Detection and Evaluation of Seawater Pipeline Corrosion in Nuclear Power Plants

    • In the aging management of nuclear power plants, the structural integrity of the seawater system pipeline is essential for the safe operation. In order to realize the daily rapid inspection of pipeline, a quantitative evaluation method based on low-frequency electromagnetic detection (LFED) technology, combined with borescope inspection for open validation was proposed in this paper. Practical inspection of operational seawater pipelines in a nuclear power plant demonstrated the effectiveness of this LFED-based detection and evaluation approach. The results indicate that two suspected signals were detected via LFED. Subsequent borescope measurements revealed their wall thicknesses of 6.58 mm and 3.25 mm, corresponding to actual wall thickness losses of 17.8% and 59.3%, respectively. The LFED method showed an error margin of 5%, confirming its strong defect detection capability and quantitative evaluation accuracy. The low-frequency electromagnetic testing technology can be applied to online pipeline corrosion monitoring and condition assessment, providing effective technical support for the structural integrity of metallic pipelines in nuclear power plants.
    • loading

    Catalog

      Turn off MathJax
      Article Contents

      /

      DownLoad:  Full-Size Img  PowerPoint
      Return